contact
H Series Open loop Current Sensor - HS3V 2000 H00 - Image 1

Ultra High Accuracy Hall Effect Direct Current Sensors

  • Open loop current sensor using the Hall effect
  • Galvanic separation between primary and secondary
  • Insulating plastic case recognized according to UL 94-V0
  • No insertion losses
  • Small size
  • Standards:
  • IEC 60664-1:2020
  • IEC 61800-5-1:2022
  • IEC 62109-1:2010

The current sensor series can perform electronic measurement of direct current, alternating current or pulse current, while ensuring electrical isolation between the primary and secondary circuits.
The instantaneous voltage output range of these sensors is +/-4 V, and they are powered by a +/-15 V bipolar power supply. The DC bandwidth is 25 KHz.
Current sensor is designed based on the Hall effect open-loop technology and is specifically tailored for industrial applications.

Specification

Primary nominal RMS current (A) 2000
Measuring range (A) ±5500
Supply voltage (V) ±15
Secondary output ±4V
Accuracy (%) ±1
Output bandwidth 25
Operating temperature (°C) -40~85
Copper busbar (mm) 64 x 21 mm
PCB
Others MOLEX 5045-04A