contact
H Series Open loop Current Sensor - HS1V 50 H05 - Image 1

Through-Hole install DC open loop Current Sensor

  • Open loop sensor using the Hall Effect
  • Output voltage is proportional to supply voltage
  • Galvanic separation between primary and secondary
  • Insulating plastic case recognized according to UL 94-V0
  • No insertion loss
  • Small size
  • Standards:IEC 60664-1:2020, IEC 61800-5-1:2022, IEC 62109-1:2010


Ipn 50A, 100A, 200A, 300A, 400A, 500A, 600A
Measure range about 4*ipn
Working voltage(supply voltage of the sensor): DC ±12V or ±15V
Output: ±4V 
Linearity: class 0.5 (±0.5%)
Accuracy: class1 (±1%)
Square perforation, mainly measure copper conductor current.
Advantage:
Non-contact measuring way, excellent accuracy, low power consumption, good current overload capability, easy use, high reliability and long term usage with your system.
We can customize different sensor according to the users requirements.

Specification

Primary nominal RMS current (A) 50
Measuring range (A) ±150
Supply voltage (V) ±12...15
Secondary output ±4V
Accuracy (%) ±1.0
Output bandwidth 50
Operating temperature (°C) -40~105
Copper busbar (mm) 20x10 mm
PCB
Others MOLEX 5045-04A