Ipn 50A, 100A, 200A, 300A, 400A, 500A, 600A
Measure range about 4*ipn
Working voltage(supply voltage of the sensor): DC ±12V or ±15V
Output: ±4V
Linearity: class 0.5 (±0.5%)
Accuracy: class1 (±1%)
Square perforation, mainly measure copper conductor current.
Advantage:
Non-contact measuring way, excellent accuracy, low power consumption, good current overload capability, easy use, high reliability and long term usage with your system.
We can customize different sensor according to the users requirements.
| Primary nominal RMS current (A) | 50 |
|---|---|
| Measuring range (A) | ±150 |
| Supply voltage (V) | ±12...15 |
| Secondary output | ±4V |
| Accuracy (%) | ±1.0 |
| Output bandwidth | 50 |
| Operating temperature (°C) | -40~105 |
| Copper busbar (mm) | 20x10 mm |
| PCB | |
| Others | MOLEX 5045-04A |